Transformer
Protector™ Tests
In
2002 and 2004, two series of tests
were performed to provoke a transformer
explosion under the worst conditions. An
electrical arc between electrodes
located inside the oil was ignited
for the 62 tests. The aim was to:
• Prove
the Transformer Protector efficiency
for pressure gradients up to 4,000
bar/sec
(58,000 psi/sec)
• Compare
the MTH preliminary calculations
with real cases of transformer
faults
• Increase
knowledge on the electrical arc inside
oil
• Calculate the pressure
wave propagation
• Measure
the operation of traditional transformer
protections
• Measure
and define a law for gas generation
volume during
short-circuit
Tests
at Electricité de
France (EDF), 2002 Click
for document #6
The
EDF High Voltage Laboratory
has performed 28 tests on
a 160 KVA transformer. Electrical
arcs were ignited with current
faults from 2.5 to 7.5 kilo
Amperes, arc energies went
up to 300 kilo Joules and
pressure gradients varied
from 200 to 1,200 bar/second
(2,900 to 17,400 psi/sec).
During those tests, the rapid
gas expansion generated by
the oil decomposition before
the arc was filmed (cf. side
picture). Also, several gauges
located around the tank measured
the pressure waves that followed
the gas creation.
|
Gas
generated during rupture
of insulation before
the electrical arc inside
the tank Video
|
|
|
|
|
|
|
The
CEPEL High Voltage Laboratory
has performed 34 tests on
3 transformers of 6, 10 and
20 MVA with current faults
up to 15 kilo Amperes and
energies up to 2,4 Mega Joules.
Half of the tests were realized
under vacuum conditions to
measure the total volume
of gas produced during the
arc generation. Different
ignition locations for the
arc were chosen to study
the Transformer Protector
behavior (see picture).
A in
front of the Depressurization
Set
B at the opposite
side
C diametrically
opposed to the Transformer
Protector Decompression Chamber
The
measurements taken, enabled
a study of the pressure wave
propagation.
|
|
|

Results
| • |
The
pressure gradients
and tank depressurization
encountered in the
tests were in agreement
with the values calculated
beforehand using
the MTH model. Click
for documents #1-4 |
• |
The efficiency of the Transformer Protector was demonstrated. As shown,
the Transformer Protector absorbs a pressure gradient of 3,900 bar/sec
(56,500 psi/sec) and the tank pressure returns to the Rupture Disk
set point only 3 milliseconds after operation. |
• |
The adjoining graph illustrates that the stronger the short-circuit is,
the faster the Transformer Protector reduces the pressure inside the
tank. This exceptional efficiency of the Transformer Protector was
already emphasized in 2001, publication. Click
for document #3 |
• |
The Transformer Protector operational parameters are independent from the
arc position inside the tank. Even for the arcs located in position
C, the pressure wave propagated and always activated the Transformer
Protector before the tank could explode. |
• |
Analyses showed that the MTH Model results and especially the Pressure
Wave Propagation matched very closely the tests measurements. |
• |
All flammable gases created by the electrical arc were always exhausted
from the Oil-Gas Separation Tank at the ambient temperature to atmosphere,
and were never set on fire. Therefore, it was demonstrated that gas
self-ignition to the atmosphere is impossible. |
• |
During all the tests, the Buchholz pressure and gas signals were never
activated as the speed of the phenomena is too fast for these devices. |
|
Pressure
variation during
Transformer Protector
Activation
|
Pressure
variation during
Transformer Protector Activation
|

Activation
time versus Energy
|
Test
Certificate
The
Transformer Protector
activated successfully
during the 62 tests,
depressurized the transformer
and prevented the tank
explosion and permanent
deformation. CEPEL
provided a Test Attestation
for the 34 tests carried
out at their High Voltage
Laboratory. Click
for document #15
|
|